| Software Compatibility | Works with all versions of CBAS: Professional, Commercial, and Utility. |
|---|---|
| Power Requirements | 40VA @ 24 Vac 50/60 Hz Class 2 transformer |
| Point Configuration | All points software configurable as analog inputs, binary inputs, analog outputs, or binary outputs. |
| Analog Output Specifcations | 0-10 Vdc voltage type |
| Binary Output Specifications | 24 Vdc @ 50 mA |
| Analog Input Specifications | 10K Ohm TYPE III thermistor 0-10 Vdc 4-20 mA 0-32K Ohm resistive (scalable) |
| Binary Input Specifications | Dry contact – switch closure Pulse dry contact 5Hz max repitition rate, 100 msec (min) pulse width |
| Voltage Protection | 250 Vac on each point terminal |
| Electrical Connections | Barrier terminal block 18 -24 AWG 24 Vdc loop source terminals (1.28 Amps maximum) |
| Internet Capability | IP addressable on-board web server |
| Communication Ports | 10 Mbps RJ-45 Ethernet TCP/IP, 100 meter maximum distance One RS485 CBAS communication 9600 Baud One RS485 interface port 9600 Baud Local hand held terminal |
| Microprocessor | Intel 386 25 MHz, 3 MB Flash, 1MB SRAM 2K NVRAM Real time clock with 10 year data retention |
| Dimensions | 6.5” W x 10.375” L x 1.25” H |
| Mounting | Mount in NEMA rated enclosure |
| Shipping Weight | 5 lbs. |
| Environmental | 32 – 158 Deg. F, 10 – 90 %RH non-condensing |
| Agency Compliance | E195258 UL 916 (PAZX) Energy Management Equipment Canadian Standard C22.2 No. 205-M1983 E231285 UL 61010C-1 (QUYZ) Electrical Process Control Equipment Canadian Standard C22.2 No. 1010 CE IEC 61010-1 (1990) with Amendments 1 (1992) and 2 (1995) |