My Runtime Point Logic is giving me wrong numbers, whats wrong?
Logic on a runtime point does not see it’s own value. This is probably because the point is being displayed in hours and not minutes. CBAS stores the runtime internally in minutes. The user can pick to display it in Hours. But when using a runtime point in logic you MUST enter the number you want in minutes. The units will probably show hours in the logic statement but the number MUST BE IN MINUTES.