How do I change an Opto Controller to a Basnet TCP/IP controller?
- Start by creating a BASNet CI1 Channel in an empty (not the final) location.
- Using Utility Mode (..cbas.exe /mode=utility), go to SYSTEM â–º CONTROLLER AND CHANNEL MAINTENANCE â–º COPY OPTO CHANNEL TO CNET CHANNEL. Select the original channel, and then choose the newly created channel.
- You will now have two channels with the same controllers on them.
- Erase the old OPTO channel by going to DATABASE â–º REMOVE A CHANNEL.
- Add a new BASNet 485 over TCP/IP channel on the Host or Secondary ports of the Internet Controller you wish to configure.
- Go to DATABASE â–º MOVE A CONTROLLER. Select the BASNet CI1 Channel to move from and the BASNet 485 TCP/IP to move to. Move your controllers to the relative position they are in.
- Delete the BASNet CI1 Channel by going to DATABASE â–º REMOVE A CHANNEL.
- Was this article helpful?
- Yes 0 people found this article helpful.
- No 0 people did not find this article helpful.