What is the DDC1/C1 Voltage Input scale?

On the DDC1 and C1, the scale is 1.00 to 4.095 Volts.

Here’s how you set your scale on the Temp and Humidity points 4-20mA:

  • 1.000 Volts = 0.0%RH/ 1.0 DEGF
  • 4.095 Volts = 100.0% RH/ 100.0 DEGF
  • Was this article helpful?
  • Yes 0 people found this article helpful.
  • No 0 people did not find this article helpful.
  • Give us feedback